p0748 CU invert digital outputs / CU DO inv
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2201, 2242
Min:
-
Max:
-
Factory setting:
0000 bin
Description: Setting to invert the signals at the digital outputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 DO 0 (NO: X134. 19 / NC: X134. 18) Inverted Not inverted -
01 DO 1 (NO: X134. 21) Inverted Not inverted -
02 DO 2 (NO: X134. 24) Inverted Not inverted -
03 DO 3 (NO: X134. 51) Inverted Not inverted -
Note
DO: Digital Output
Relay output: NO = normally open, NC = normally closed
r0751.0...11 BO: CU analog inputs status word / CU AI status word
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2251, 2252
Min:
-
Max:
-
Factory setting:
-
Description: Display and binector output for the status of the analog inputs.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Analog input AI0 wire breakage Yes No -
01 Analog input AI1 wire breakage Yes No -
02 Analog input AI2 wire breakage Yes No -
03 Analog input AI3 wire breakage Yes No -
08 Analog input AI0 no wire breakage Yes No -
09 Analog input AI1 no wire breakage Yes No -
10 Analog input AI2 no wire breakage Yes No -
11 Analog input AI3 no wire breakage Yes No -
Note
AI: Analog Input
r0752[0...3] CO: CU analog inputs input voltage/current actual / CU AI U/I_inp act
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p0514 Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
-
Max:
-
Factory setting:
-
Description: Displays the actual input voltage in V when set as voltage input.
Displays the actual input current in mA when set as current input and with the load resistor switched in.
Displays the actual temperature in °C when set as temperature sensor and the voltage divider is switched in.
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 431