p0819[0...2] Copy Drive Data Set DDS / Copy DDS
Access level: 2 Calculated: - Data type: Unsigned8
Can be changed: C2(15) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 8565
Min:
0
Max:
3
Factory setting:
0
Description: Copies one Drive Data Set (DDS) into another.
Index: [0] = Source Drive Data Set
[1] = Target Drive Data Set
[2] = Start copying procedure
Dependency: See also: r3996
NOTICE
When the drive data sets are copied, short-term communication interruptions may occur.
Note
Procedure:
1. In Index 0, enter which drive data set is to be copied.
2. In index 1, enter the drive data set data that is to be copied into.
3. Start copying: set index 2 from 0 to 1.
p0819[2] is automatically set to 0 when copying is completed.
p0820[0...n] BI: Drive Data Set selection DDS bit 0 / DDS select., bit 0
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 8565
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to select the Drive Data Set, bit 0 (DDS, bit 0).
Dependency: See also: r0051, p0826, r0837
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0821[0...n] BI: Drive Data Set selection DDS bit 1 / DDS select., bit 1
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 8565, 8570
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to select the Drive Data Set, bit 1 (DDS, bit 1).
Dependency: See also: r0051, r0837
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0826[0...n] Motor changeover motor number / Mot_chng mot No.
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
3
Factory setting:
0