Dependency: The following applies: p2182 < p2183 < p2184
See also: p2182, p2183, p2189, p2190
See also: A07926
Note
In order that the load monitoring can reliably respond, the speed threshold p2184 should always be set higher than the
maximum motor speed to be monitored.
p2185[0...n] Load monitoring torque threshold 1 upper / M_thresh 1 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
10000000.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2185 > p2186
See also: p2182, p2186
See also: A07926
Note
The upper envelope curve is defined by p2185, p2187 and p2189.
p2186[0...n] Load monitoring torque threshold 1 lower / M_thresh 1 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2186 < p2185
See also: p2182, p2185
See also: A07926
Note
The lower envelope curve is defined by p2186, p2188 and p2190.
p2187[0...n] Load monitoring torque threshold 2 upper / M_thresh 2 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
10000000.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2187 > p2188
See also: p2183, p2188
See also: A07926
Note
The upper envelope curve is defined by p2185, p2187 and p2189.
Parameters
7.3 Parameters
SINAMICS G120XA converter