EasyManua.ls Logo

Siemens SINAMICS G120XA - Load Monitoring Torque Threshold 1 Lower; M_Thresh 1 Lower; Load Monitoring Torque Threshold 1 Upper; M_Thresh 1 Upper; Load Monitoring Torque Threshold 2 Upper; M_Thresh 2 Upper

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Dependency: The following applies: p2182 < p2183 < p2184
See also: p2182, p2183, p2189, p2190
See also: A07926
Note
In order that the load monitoring can reliably respond, the speed threshold p2184 should always be set higher than the
maximum motor speed to be monitored.
p2185[0...n] Load monitoring torque threshold 1 upper / M_thresh 1 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
10000000.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2185 > p2186
See also: p2182, p2186
See also: A07926
Note
The upper envelope curve is defined by p2185, p2187 and p2189.
p2186[0...n] Load monitoring torque threshold 1 lower / M_thresh 1 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2186 < p2185
See also: p2182, p2185
See also: A07926
Note
The lower envelope curve is defined by p2186, p2188 and p2190.
p2187[0...n] Load monitoring torque threshold 2 upper / M_thresh 2 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
10000000.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2187 > p2188
See also: p2183, p2188
See also: A07926
Note
The upper envelope curve is defined by p2185, p2187 and p2189.
Parameters
7.3 Parameters
SINAMICS G120XA converter
598 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB