EasyManua.ls Logo

Siemens SINAMICS G120XA - BI: Binector-Connector Converter Status Word 3; Bin;Con ZSW3; BI: Binector-Connector Converter Status Word 4; Bin;Con ZSW4

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
p2082[0...15] BI: Binector-connector converter status word 3 / Bin/con ZSW3
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2472
Min:
-
Max:
-
Factory setting:
0
Description: Selects bits to be sent to the PROFIdrive controller.
The individual bits are combined to form free status word 3.
Index: [0] = Bit 0
[1] = Bit 1
[2] = Bit 2
[3] = Bit 3
[4] = Bit 4
[5] = Bit 5
[6] = Bit 6
[7] = Bit 7
[8] = Bit 8
[9] = Bit 9
[10] = Bit 10
[11] = Bit 11
[12] = Bit 12
[13] = Bit 13
[14] = Bit 14
[15] = Bit 15
Dependency: See also: p2088, r2089
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p2083[0...15] BI: Binector-connector converter status word 4 / Bin/con ZSW4
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2472
Min:
-
Max:
-
Factory setting:
0
Description: Selects bits to be sent to the PROFIdrive controller.
The individual bits are combined to form free status word 4.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 569