p11153 CI: Free tec_ctrl 1 setpoint signal source / Ftec1 setp s_s
Access level: 2 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the setpoint of the free technology controller 1.
p11157 Free tec_ctrl 1 setpoint ramp-up time / Ftec1 setp t_r-up
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description: Sets the ramp-up time for the free technology controller 1.
Dependency: See also: p11158
Note
The ramp-up time is referred to 100 %.
p11158 Free tec_ctrl 1 setpoint ramp-down time / Ftec1 setp t_r-dn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0.00 [s]
Max:
650.00 [s]
Factory setting:
1.00 [s]
Description: Sets the ramp-down time of the free technology controller 1.
Dependency: See also: p11157
Note
The ramp-down time is referred to 100 %.
r11160 CO: Free tec_ctrl 1 setpoint after ramp-function generator / Ftec1 setp aft RFG
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_3 Unit selection: p11126 Function diagram: 7030
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the setpoint after the ramp-function generator of the free technology controller 1.
p11163 Free tec_ctrl 1 system deviation inversion / Ftec1 sys_dev inv
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0
Max:
1
Factory setting:
0
Description: Sets the inversion of the system deviation of the free technology controller 1.
The setting depends on the type of control loop.
Value: 0: No inversion
Parameters
7.3 Parameters
SINAMICS G120XA converter
694 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB