p11285 Free tec_ctrl 2 integral time / Ftec2 Tn
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0.000 [s]
Max:
10000.000 [s]
Factory setting:
30.000 [s]
Description: Sets the integral time (I component, integrating time constant) of the free technology controller 2.
Note
Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
p11291 CO: Free tec_ctrl 2 limit maximum / Ftec2 lim max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
100.00 [%]
Description: Sets the maximum limit of the free technology controller 2.
Dependency: See also: p11292
Note
The maximum limit must always be greater than the minimum limit (p11291 > p11292).
p11292 CO: Free tec_ctrl 2 limit minimum / Ftec2 lim min
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
0.00 [%]
Description: Sets the minimum limit of the free technology controller 2.
Dependency: See also: p11291
Note
The maximum limit must always be greater than the minimum limit (p11291 > p11292).
p11293 Free tec_ctrl 2 limit ramp-up/ramp-down time / Ftec2 lim r-u/r-dn
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7030
Min:
0.00 [s]
Max:
100.00 [s]
Factory setting:
1.00 [s]
Description: Sets the ramp-up and ramp-down time for the maximum and minimum limit (p11291, p11292) of the free technology
controller 2.
Dependency: See also: p11291, p11292
Note
The ramp-up/ramp-down times are referred to 100%.
Parameters
7.3 Parameters
SINAMICS G120XA converter
704 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB