Function description
After the pipe filling is enabled, you can select from the following two filling modes:
Time mode: p29611 = 0
The converter fills the pipe with a low speed for a specified time (p29613) and then changes
the speed to the setpoint.
3LSHILOOLQJ
VSHHG
6SHHG
3LSHILOOLQJWLPH
2SHUDWLRQ
W
S
S
Pressure mode: p29611 = 1
The converter fills the pipe according to the PID feedback from the pressure sensor. The
filling stops when the actual pressure (r2272) the threshold (p29614) for a specified time
(p29615).
S
3LSHILOOLQJPRQLWRULQJWLPH
3UHVVXUH
3LSHILOOLQJ
WKUHVKROG
3LSHILOOLQJ
VSHHG
6SHHG
2SHUDWLRQ
S
W
S
W
Note
Priority of frost protection, condensation protection, deragging and pipe filling
The priority of functions is as follows: frost protection > condensation protection > deragging >
pipe filling.
Advanced commissioning
6.3 Pump control
SINAMICS G120XA converter
216 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB