p2179[0...n] Output load identification current limit / Outp_ld iden I_lim
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: p2002 Dynamic index: DDS, p0180
Unit group: 6_2 Unit selection: p0505 Function diagram: 8022
Min:
0.00 [Arms]
Max:
1000.00 [Arms]
Factory setting:
0.00 [Arms]
Description: Sets the current limit for output load identification.
A missing output load is displayed using the "Output load not available" message (r2197.11 = 1).
This message is output with a delay time (p2180).
Dependency: See also: p2180
NOTICE
For synchronous motors the output current can be almost zero under no load conditions.
Note
Missing output load is signaled in the following cases:
- the motor is not connected.
- a phase failure has occurred.
p2180[0...n] Output load detection delay time / Out_load det t_del
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 8022
Min:
0 [ms]
Max:
10000 [ms]
Factory setting:
2000 [ms]
Description: Sets the delay time for the message "output load not available" (r2197.11 = 1).
Dependency: See also: p2179
p2181[0...n] Load monitoring response / Load monit resp
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 8013
Min:
0
Max:
8
Factory setting:
0
Description: Sets the response when evaluating the load monitoring.
Value: 0: Load monitoring disabled
1: A07920 for torque/speed too low
2: A07921 for torque/speed too high
3: A07922 for torque/speed out of tolerance
4: F07923 for torque/speed too low
5: F07924 for torque/speed too high
6: F07925 for torque/speed out of tolerance
7: Pump/fan load monitoring as alarm
8: Pump/fan load monitoring as fault
Dependency: See also: p2182, p2183, p2184, p2185, p2186, p2187, p2188, p2189, p2190, p2192, p2193, r2198, p3230, p3231
See also: A07891, A07892, A07893, F07894, F07895, F07896, F07898, A07920, A07921, A07922, F07923, F07924,
F07925