● ST RT OP: setting same as STIL ROT.
After the motor data identification, the motor accelerates to the current setpoint.
● STILL OP: setting same as STILL.
After the motor data identification, the motor accelerates to the current setpoint.
Complete quick commissioning:
● Switch over the display using an arrow key: nO → YES
● Press the OK key.
You have completed quick commissioning.
❒
5.4.7 Expert
Select the motor standard:
● KW / 50HZ: IEC
● HP / 60HZ: NEMA, US units
● KW / 60HZ: NEMA, SI units
Specify the overload capability of the converter:
● HIGH OVL: Duty cycle with "High Overload"
● LOW OVL: Duty cycle with "Low Overload"
Load cycles and overload capability (Page 863)
Set the converter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
● INDUCT: Third-party induction motor
● 1L… IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
● 1LE1 IND 100: 1LE1 . 9
● 1PC1 IND: 1PC1
Depending on the converter, the motor list in BOP‑2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The
converter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor data
from p0304 and higher from the rating plate.
87 Hz motor operation The BOP‑2 only indicates this step if you selected IEC as the motor
standard (EUR/USA, P100 = kW 50 Hz).
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120XA converter
118 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB