p0301[0...n] Motor code number selection / Mot code No. sel
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: C2(1, 3) Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
65535
Factory setting:
0
Description: The parameter is used to select a motor from a motor parameter list.
When changing the code number (with the exception to the value 0), all of the motor parameters are pre-assigned from
the internally available parameter lists.
Dependency: Code numbers can only be selected for motor types that correspond to the motor type selected in p0300.
See also: p0300
Note
The motor code number can only be changed if the matching catalog motor was first selected in p0300.
When selecting a catalog motor (p0300 >= 100), drive commissioning can only be exited if a code number is selected.
If a change is made to a non-catalog motor, then the motor code number should be reset (p0301 = 0).
p0304[0...n] Rated motor voltage / Mot U_rated
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C2(1, 3) Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: 6301, 6724
Min:
0 [Vrms]
Max:
20000 [Vrms]
Factory setting:
0 [Vrms]
Description: Sets the rated motor voltage (rating plate).
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is pre-
assigned to match the power unit.
p0305[0...n] Rated motor current / Mot I_rated
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C2(1, 3) Scaling: - Dynamic index: MDS, p0130
Unit group: - Unit selection: - Function diagram: 6301
Min:
0.00 [Arms]
Max:
10000.00 [Arms]
Factory setting:
0.00 [Arms]
Description: Sets the rated motor current (rating plate).
NOTICE
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
If p0305 is changed during quick commissioning (p0010 = 1), then the maximum current p0640 is pre-assigned
accordingly.
Note
When the parameter value is entered the connection type of the motor (star-delta) must be taken into account.
Once the Control Unit has booted for the first time or if the factory settings have been restored, the parameter is pre-
assigned to match the power unit.
Parameters
7.3 Parameters
SINAMICS G120XA converter
390 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB