Siemens SINAMICS G120XA - CO: Profidrive PZD Receive Word; PZD Recv Word; Fieldbus Interface Monitoring Time; Fieldbus T_Monit

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Enable operation Yes No -
04 Enable ramp-function generator Yes No -
05 Start ramp-function generator Yes No -
06 Enable speed setpoint Yes No -
07 Acknowledge fault Yes No -
08 Jog bit 0 Yes No 3030
09 Jog bit 1 Yes No 3030
10 Master control by PLC Yes No -
NOTICE
The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note
OC: Operating condition
p2040 Fieldbus interface monitoring time / Fieldbus t_monit
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0 [ms]
Max:
1999999 [ms]
Factory setting:
1000 [ms]
Description: Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency: See also: F01910
Note
p2040 = 0:
Monitoring is deactivated.
For p2030 = 2 (Modbus RTU) or p2030 = 5 (BACnet MS/TP) the following deviation applies:
Factory setting: 10000
r2050[0...11] CO: PROFIdrive PZD receive word / PZD recv word
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: 4000H Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2440, 2468,
9360
Min:
-
Max:
-
Factory setting:
-
Description: Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Parameters
7.3 Parameters
SINAMICS G120XA converter
562 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB