01 OC / OFF2 Yes No -
02 OC / OFF3 Yes No -
03 Enable operation Yes No -
04 Enable ramp-function generator Yes No -
05 Start ramp-function generator Yes No -
06 Enable speed setpoint Yes No -
07 Acknowledge fault Yes No -
08 Jog bit 0 Yes No 3030
09 Jog bit 1 Yes No 3030
10 Master control by PLC Yes No -
NOTICE
The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note
OC: Operating condition
p2040 Fieldbus interface monitoring time / Fieldbus t_monit
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0 [ms]
Max:
1999999 [ms]
Factory setting:
1000 [ms]
Description: Sets the monitoring time to monitor the process data received via the fieldbus interface.
If no process data is received within this time, then an appropriate message is output.
Dependency: See also: F01910
Note
p2040 = 0:
Monitoring is deactivated.
For p2030 = 2 (Modbus RTU) or p2030 = 5 (BACnet MS/TP) the following deviation applies:
Factory setting: 10000
r2050[0...11] CO: PROFIdrive PZD receive word / PZD recv word
Access level: 3 Calculated: - Data type: Integer16
Can be changed: - Scaling: 4000H Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2440, 2468,
9360
Min:
-
Max:
-
Factory setting:
-
Description: Connector output to interconnect PZD (setpoints) with word format received from the fieldbus controller.
Parameters
7.3 Parameters
SINAMICS G120XA converter
562 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB