Object
property
Object type
Binary In‐
put
Binary Out‐
put
Binary Val‐
ue
Analog In‐
put
Analog
Output
Analog
Value
Multi-State
Input
Octet
String Val‐
ues
Priority_Array X X* X X*
Relinquish_De‐
fault
X X* X X*
Polarity X X
Active_Text X X X
Inactive_Text X X X
COV_Increment X X X
State_Text X
Num‐
ber_of_States
X
* for command values only (access type C)
Note
Access types are available in the following versions
● C: Executable
● R: Readable
● W: Writable
Binary Input Objects
In‐
stance
ID
Object name Description Possible val‐
ues
Text active /
text inactive
Access
type
Parameter
BI0 DI0 ACT State of DI 0 ON/OFF ON/OFF R r0722.0
BI1 DI1 ACT State of DI 1 ON/OFF ON/OFF R r0722.1
BI2 DI2 ACT State of DI 2 ON/OFF ON/OFF R r0722.2
BI3 DI3 ACT State of DI 3 ON/OFF ON/OFF R r0722.3
BI4 DI4 ACT State of DI 4 ON/OFF ON/OFF R r0722.4
BI5 DI5 ACT State of DI 5 ON/OFF ON/OFF R r0722.5
BI7 DI7 ACT State of AI 1 - used as DI ON/OFF ON/OFF R r0722.11
BI8 DI8 ACT State of AI 2 - used as DI ON/OFF ON/OFF R r0722.12
BI10 DO0 ACT State of DO 0 (relay 1) ON/OFF ON/OFF R read r747.0
BI11 DO1 ACT State of DO 1 (relay 2) ON/OFF ON/OFF R read r747.1
BI12 DO2 ACT State of DO2 (relay 3) ON/OFF ON/OFF R read r747.2
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 187