Analog Output Objects
In‐
stance
ID
Object name Description Unit Range Access
type
Parameter
AO0 ANALOG OUTPUT 0 Value of AO0 % converter-depend‐
ent
C p0791.0
AO1 ANALOG OUTPUT 1 Value of AO1 % converter-depend‐
ent
C p0791.1
Analog Value Objects
In‐
stance
ID
Object name Description Unit Range Access
type
Parameter
AV0
OUT FREQ HZ
Output frequency (Hz) Hz converter-depend‐
ent
R r0024
AV1 OUT FREQ PCT Output frequency (%) % converter-depend‐
ent
R HIW
AV2 OUTPUT SPEED Motor speed RPM converter-depend‐
ent
R r0022
AV3 DC BUS VOLT DC-link voltage. V converter-depend‐
ent
R r0026
AV4 OUTPUT VOLT Output voltage V converter-depend‐
ent
R r0025
AV5 CURRENT Motor current A converter-depend‐
ent
R r0027
AV6 TORQUE Motor torque Nm converter-depend‐
ent
R r0031
AV7 POWER Motor power kW converter-depend‐
ent
R r0032
AV8 DRIVE TEMP Heat sink temperature °C converter-depend‐
ent
R r0037
AV9
MOTOR TEMP
Measured or calculated motor
temperature
°C converter-depend‐
ent
R r0035
AV10
KWH NR
Cumulative converter energy
consumption (cannot be reset!)
kWh converter-depend‐
ent
R r0039
AV12
INV RUN TIME
Motor's operating hours (is reset
by entering "0")
h 0 … 4294967295 W p0650
AV13
INV Model
Code number of Power Module --- converter-depend‐
ent
R r0200
AV14
INV FW VER
Firmware version --- converter-depend‐
ent
R r0018
AV15 INV POWER Rated power of the converter kW converter-depend‐
ent
R r0206
AV16 SPEED
STPT 1
Reference speed of the convert‐
er
RPM 6.0 … 210000 W p2000
AV17 FREQ SP PCT Setpoint 1 (when controlling via
BACnet)
% -199.99 … 199.99 C HSW
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
190 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB