EasyManua.ls Logo

Siemens SINAMICS G120XA - Analog Output Objects; Analog Value Objects

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Output Objects
In‐
stance
ID
Object name Description Unit Range Access
type
Parameter
AO0 ANALOG OUTPUT 0 Value of AO0 % converter-depend‐
ent
C p0791.0
AO1 ANALOG OUTPUT 1 Value of AO1 % converter-depend‐
ent
C p0791.1
Analog Value Objects
In‐
stance
ID
Object name Description Unit Range Access
type
Parameter
AV0
OUT FREQ HZ
Output frequency (Hz) Hz converter-depend‐
ent
R r0024
AV1 OUT FREQ PCT Output frequency (%) % converter-depend‐
ent
R HIW
AV2 OUTPUT SPEED Motor speed RPM converter-depend‐
ent
R r0022
AV3 DC BUS VOLT DC-link voltage. V converter-depend‐
ent
R r0026
AV4 OUTPUT VOLT Output voltage V converter-depend‐
ent
R r0025
AV5 CURRENT Motor current A converter-depend‐
ent
R r0027
AV6 TORQUE Motor torque Nm converter-depend‐
ent
R r0031
AV7 POWER Motor power kW converter-depend‐
ent
R r0032
AV8 DRIVE TEMP Heat sink temperature °C converter-depend‐
ent
R r0037
AV9
MOTOR TEMP
Measured or calculated motor
temperature
°C converter-depend‐
ent
R r0035
AV10
KWH NR
Cumulative converter energy
consumption (cannot be reset!)
kWh converter-depend‐
ent
R r0039
AV12
INV RUN TIME
Motor's operating hours (is reset
by entering "0")
h 0 … 4294967295 W p0650
AV13
INV Model
Code number of Power Module --- converter-depend‐
ent
R r0200
AV14
INV FW VER
Firmware version --- converter-depend‐
ent
R r0018
AV15 INV POWER Rated power of the converter kW converter-depend‐
ent
R r0206
AV16 SPEED
STPT 1
Reference speed of the convert‐
er
RPM 6.0 … 210000 W p2000
AV17 FREQ SP PCT Setpoint 1 (when controlling via
BACnet)
% -199.99 … 199.99 C HSW
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
190 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB

Table of Contents

Related product manuals