Note
For bit 12:
This bit is reset after the fault cause disappears, even if the fault itself is still present.
r2199.0...5 CO/BO: Status word monitoring 3 / ZSW monitor 3
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2537
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the third status word of the monitoring functions.
Bit field: Bit Signal name 1 signal 0 signal FP
00 |n_act| < speed threshold value 3 Yes No 8010
01 f or n comparison value reached or exceeded Yes No 8010
04 Speed setpoint - actual value deviation in tolerance t_on Yes No 8011
05 Ramp-up/ramp-down completed Yes No 8011
Note
For bit 00:
The speed threshold value 3 is set in p2161.
For bit 01:
The comparison value is set in p2141. We recommend setting the hysteresis (p2142) for canceling the bit to a value
lower than that in p2141. Otherwise, the bit is not reset.
p2200[0...n] BI: Technology controller enable / Tec_ctrl enable
Access level: 2 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7958
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to switch in/switch out the technology controller.
The technology controller is switched in with a 1 signal.
p2201[0...n] CO: Technology controller fixed value 1 / Tec_ctrl fix val1
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Function diagram: 7950, 7951
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
10.00 [%]
Description: Sets the value for fixed value 1 of the technology controller.
Dependency: See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2202[0...n] CO: Technology controller fixed value 2 / Tec_ctr fix val 2
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: DDS, p0180
Unit group: 9_1 Unit selection: p0595 Function diagram: 7950, 7951
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
20.00 [%]
Parameters
7.3 Parameters
SINAMICS G120XA converter
602 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB