p0205 Power unit application / PU application
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C2(1, 2) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
7
Factory setting:
0
Description: The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value: 0: Load duty cycle with high overload for vector drives
1: Load duty cycle with low overload for vector drives
6: S1 duty cycle (for internal use)
7: S6 duty cycle (for internal use)
Dependency: See also: r3996
NOTICE
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note
When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application (p0500)
and the control mode (p1300) are pre-assigned according to the selected application. The parameter has no influence
when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
p0205 Power unit application / PU application
CUG120XA_USS
(PM330)
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C2(1, 2) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
1
Factory setting:
1
Description: The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value: 0: Load duty cycle with high overload for vector drives
1: Load duty cycle with low overload for vector drives
Dependency: See also: r3996
NOTICE
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note
When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application (p0500)
and the control mode (p1300) are pre-assigned according to the selected application. The parameter has no influence
when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
r0206[0...4] Rated power unit power / PU P_rated
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: - Dynamic index: -
Unit group: 14_6 Unit selection: p0100 Function diagram: -
Min:
- [kW]
Max:
- [kW]
Factory setting:
- [kW]
Description: Displays the rated power unit power for various load duty cycles.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 379