6.6 Motor control
Overview
The converter has two alternative methods to ensure the motor speed follows the configured
speed setpoint:
U/f control
Vector control
6.6.1 Reactor, filter and cable resistance at the converter output
Overview
Components between the converter and the motor influence the closed-loop control quality of
the converter:
Output reactor
In the factory setting, the converter assumes for the motor data identification that no output
reactor is connected at the converter output.
Motor cable with unusually high cable resistance.
For the motor data identification, the converter assumes a cable resistance = 20 % of the
stator resistance of the cold motor.
Function description
You must correctly set the components between the converter and motor to achieve an
optimum closed-loop control quality
Procedure
1. Set p0010 = 2.
2. Set the cable resistance in p0352.
3. Set p0230 to the appropriate value.
4. Set p0235 to the appropriate value.
5. Set p0010 = 0.
6. Carry out the quick commissioning and the motor identification again.
Quick commissioning using the BOP-2 operator panel (Page 110)
You have set the reactor, filter and cable resistance between the converter and motor.
Advanced commissioning
6.6 Motor control
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 273