p1101[0...n] Skip speed bandwidth / n_skip bandwidth
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 3050
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
0.000 [rpm]
Description: Sets the bandwidth for the skip speeds/velocities 1 to 4.
Dependency: See also: p1091, p1092, p1093, p1094
Note
The setpoint (reference) speeds are skipped (suppressed) in the range of the skip speed +/-p1101.
Steady-state operation is not possible in the skipped (suppressed) speed range. The skip (suppression) range is
skipped.
Example:
p1091 = 600 and p1101 = 20
--> setpoint speeds between 580 and 620 [rpm] are skipped.
For the skip bandwidths, the following hysteresis behavior applies:
For a setpoint speed coming from below, the following applies:
r1170 < 580 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 580 [rpm]
For a setpoint speed coming from above, the following applies:
r1170 > 620 [rpm] and 580 [rpm] <= r1114 <= 620 [rpm] --> r1119 = 620 [rpm]
p1106[0...n] CI: Minimum speed signal source / n_min s_src
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 3050
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for lowest possible motor speed.
Dependency: See also: p1080
NOTICE
The effective minimum speed is formed from p1080 and p1106.
p1110[0...n] BI: Inhibit negative direction / Inhib neg dir
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2505, 3040
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source to disable the negative direction.
Dependency: See also: p1111
p1111[0...n] BI: Inhibit positive direction / Inhib pos dir
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2505, 3040
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to disable the positive direction.
Dependency: See also: p1110
Parameters
7.3 Parameters
SINAMICS G120XA converter
480 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB