Description: Sets the configuration for messages and monitoring functions.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Enable alarm A07903 Yes No 8011
01 Load monitoring only in the 1st quadrant Yes No 8013
03 n_act > p2155 own hysteresis Yes No 8010
05 Stall monitoring for encoderless speed control Yes No -
Dependency: See also: r2197
See also: A07903
Note
For bit 00:
Alarm A07903 is output when the bit is set with r2197.7 = 0 (n_set <> n_act).
For bit 01:
When the bit is set, the load monitoring is only executed in the 1st quadrant as a result of the positive characteristic
parameters (p2182 ... p2190).
For bit 03:
When the bit is set, r2197.1 and r2197.2 are determined using separate hysteresis functions.
For bit 05:
When this bit is set, a change to open-loop speed controlled operation is only possible when the motor is stationary.
p2150[0...n] Hysteresis speed 3 / n_hysteresis 3
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: 8010, 8011,
8022
Min:
0.00 [rpm]
Max:
300.00 [rpm]
Factory setting:
2.00 [rpm]
Description: Sets the hysteresis speed (bandwidth) for the following signals:
"|n_act| < speed threshold value 3" (BO: r2199.0)
"n_set >= 0" (BO: r2198.5)
"n_act >= 0" (BO: r2197.3)
Dependency: See also: p2161, r2197, r2199
p2151[0...n] CI: Speed setpoint for messages/signals / n_set for msg
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 8011
Min:
-
Max:
-
Factory setting:
1170[0]
Description: Sets the signal source for the speed setpoint for the following messages:
"Speed setpoint - actual value deviation within tolerance t_off" (BO: r2197.7)
"Ramp-up/ramp-down completed" (BO: r2199.5)
"|n_set| < p2161" (BO: r2198.4)
"n_set > 0" (BO: r2198.5)
Dependency: See also: r2197, r2198, r2199
Parameters
7.3 Parameters
SINAMICS G120XA converter
590 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB