p2188[0...n] Load monitoring torque threshold 2 lower / M_thresh 2 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2188 < p2187
See also: p2183, p2187
See also: A07926
Note
The lower envelope curve is defined by p2186, p2188 and p2190.
p2189[0...n] Load monitoring torque threshold 3 upper / M_thresh 3 upper
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
10000000.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2189 > p2190
See also: p2184, p2190
See also: A07926
Note
The upper envelope curve is defined by p2185, p2187 and p2189.
p2190[0...n] Load monitoring torque threshold 3 lower / M_thresh 3 lower
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description: Sets the speed/torque envelope curve for load monitoring.
Dependency: The following applies: p2190 < p2189
See also: p2184, p2189
See also: A07926
Note
The lower envelope curve is defined by p2186, p2188 and p2190.
p2191[0...n] Load monitoring torque threshold no load / M_thresh no load
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: 7_1 Unit selection: p0505 Function diagram: 8013
Min:
0.00 [Nm]
Max:
20000000.00 [Nm]
Factory setting:
0.00 [Nm]
Description: Setting of the torque threshold to identify dry running operation for pumps or belt breakage for fans.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 599