Function description
Procedure
1. Insert the memory card into the converter.
2. Then switch on the converter power supply.
If there is valid parameter data on the memory card, then the converter accepts the data from
the memory card.
8.1.3.2 Manually transferring
Precondition
The converter power supply has been switched on.
No memory card is inserted in the converter.
Function description
Procedure with the BOP-2
(;75$6
)520&5'
In the "OPTIONS" menu, select "FROM CRD".
3$5$06(7
Set the number of your data backup. You can back up 99 different settings on
the memory card.
Saving the settings and series commissioning
8.1 Memory card
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 729