6.2.3.6 Mapping tables - converter data
Table 6-10 Assigning the Modbus registers to the parameters - inputs and outputs
Regis‐
ter
Description Ac‐
cess
Unit Scaling ON/OFF text/
value range
Data / parameter
Digital outputs
40200 DO 0 R/W -- 1 HIGH LOW p0730, r747.0, p748.0
40201 DO 1 R/W -- 1 HIGH LOW p0731, r747.1, p748.1
40202 DO 2 R/W -- 1 HIGH LOW p0732, r747.2, p748.2
40203 DO 3 R/W -- 1 HIGH LOW p0733, r747.3, p748.3
Analog outputs
40220 AO 0 R % 100 -100.0 … 100.0 r0774.0
40221 AO 1 R % 100 -100.0 … 100.0 r0774.1
40523 AO 0 R/W % 100 -199.99 … 199.99 p0791.0
40524 AO 1 R/W % 100 -199.99 … 199.99 p0791.1
Digital inputs
40240 DI 0 R -- 1 HIGH LOW r0722.0
40241 DI 1 R -- 1 HIGH LOW r0722.1
40242 DI 2 R -- 1 HIGH LOW r0722.2
40243 DI 3 R -- 1 HIGH LOW r0722.3
40244 DI 4 R -- 1 HIGH LOW r0722.4
40245 DI 5 R -- 1 HIGH LOW r0722.5
Analog inputs
40260 AI 0 R % 100 -300.0 … 300.0 r0755 [0]
40261 AI 1 R % 100 -300.0 … 300.0 r0755 [1]
Table 6-11 Assigning the Modbus registers to the parameters - converter data
Regis‐
ter
Description Ac‐
cess
Unit Scaling ON/OFF text/
value range
Data / parameter
40300 Powerstack number R -- 1 0 … 32767 r0200
40301 Converter firmware R -- 1 e.g. 470 r0018 / 10000
40320 Rated power R kW 100 0 … 327.67 r0206
40321 Current limit R/W A 10 10.0 … 400.0 p0640
40322 Ramp-up time R/W s 100 0.00 … 650.0 p1120
40323 Ramp-down time R/W s 100 0.00 … 650.0 p1121
40324 Reference speed R/W RPM 1 6 … 32767 p2000
Converter diagnostics
40340 Speed setpoint R RPM 1 -16250 … 16250 r0020
40341 Actual speed value R RPM 1 -16250 … 16250 r0022
40342 Output frequency R Hz 100 - 327.68 … 327.67 r0024
40343 Output voltage R V 1 0 … 32767 r0025
40344 DC-link voltage R V 1 0 … 32767 r0026
Advanced commissioning
6.2 Drive control
SINAMICS G120XA converter
156 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB