EasyManua.ls Logo

Siemens SINAMICS G120XA - Free Technology Controllers; Parameters for the Free Technology Controller 0

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.5.2 Free technology controllers
Overview
The converter has three additional technology controllers.
The three "free technology controllers" have fewer setting options compared with the PID
technology controller described above.
PID technology controller (Page 247)
Function description
(QDEOH
6HWSRLQW
$FWXDO
YDOXH

SQ
SQSQ
SQ

SQSQ
SQ

UQ
SQ
SQ
SQ
SQ
SQ

SQ
GW
G

SQ


n = 0 Free technology controller 0
n = 1 Free technology controller 1
n = 2 Free technology controller 2
Figure 6-50 Simplified function chart of the additional PID technology controllers, n = 0 … 2
The additional technology controllers allow several process variables to be simultaneously
controlled using one converter.
Example
An HVAC system with heating and cooling valves to process the air:
The main controller controls the speed of the fan drive.
The additional technology controllers control the cooling and heating via the two analog
outputs.
Parameters
Table 6-58 Parameters for the free technology controller 0
Number Name Factory setting
p11000 BI: Free tec_ctrl 0 enable 0
p11026 Free tec_ctrl 0 unit selection 1 (%)
p11027 Free tec_ctrl 0 unit reference variable 1.00
p11028 Free tec_ctrl 0 sampling time 2 (256 ms)
r11049.0...11 CO/BO: Free tec_ctrl 0 status word -
3,'
Advanced commissioning
6.5 Technology controller
SINAMICS G120XA converter
264 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB

Table of Contents

Related product manuals