p2265 Technology controller actual value filter time constant / Tec_ctrl act T
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0.000 [s]
Max:
60.000 [s]
Factory setting:
0.000 [s]
Description: Sets the time constant for the actual value filter (PT1) of the technology controller.
r2266 CO: Technology controller actual value after filter / Tec_ctr act aftFlt
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7958
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the smoothed actual value after the filter (PT1) of the technology controller.
p2267 Technology controller upper limit actual value / Tec_ctrl u_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7958
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
100.00 [%]
Description: Sets the upper limit for the actual value signal of the technology controller.
Dependency: See also: p2264, p2265, p2271
See also: F07426
NOTICE
If the actual value exceeds this upper limit, this results in fault F07426.
p2268 Technology controller lower limit actual value / Tec_ctrl l_lim act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7958
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
-100.00 [%]
Description: Sets the lower limit for the actual value signal of the technology controller.
Dependency: See also: p2264, p2265, p2271
See also: F07426
NOTICE
If the actual value falls below this lower limit, this results in fault F07426.
p2269 Technology controller gain actual value / Tech_ctrl gain act
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7958
Min:
0.00 [%]
Max:
500.00 [%]
Factory setting:
100.00 [%]
Description: Sets the scaling factor for the actual value of the technology controller.
Dependency: See also: p2264, p2265, p2267, p2268, p2271
Parameters
7.3 Parameters
SINAMICS G120XA converter
614 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB