r2379.0...7 CO/BO: Closed-loop cascade control status word / Csc_ctrl ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays the status word of the closed-loop cascade control
Bit field: Bit Signal name 1 signal 0 signal FP
00 Start external motor 1 Yes No -
01 Start external motor 2 Yes No -
02 Start external motor 3 Yes No -
03 Switch-in motor Yes No -
04 Switch-in/switch-out active Yes No -
05 All motors active Yes No -
06 Automatic replacement not possible Yes No -
07 Alarm active Yes No -
p2380[0...2] Closed-loop cascade control operating hours / Csc_ctrl op_hrs
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.0 [h]
Max:
340.28235E36 [h]
Factory setting:
0.0 [h]
Description: Displays the operating hours for the external motors.
The display can only be reset to zero.
Index: [0] = Motor 1
[1] = Motor 2
[2] = Motor 3
p2381 Closed-loop cascade control max time for continuous operation / Csc_ctrl t_max
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.1 [h]
Max:
100000.0 [h]
Factory setting:
24.0 [h]
Description: Time limit for the continuous operation of external motors.
Continuous operation is measured starting from when a motor is connected to the line voltage. It ends when a motor
is disconnected from the line.
p2382 Closed-loop cascade control operating time limit / Csc_ctrl t_max op
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.1 [h]
Max:
100000.0 [h]
Factory setting:
24.0 [h]
Description: Limit for the total operating time of external motors.
The total operating time of an external motor increases every time it is switched in.
Parameters
7.3 Parameters
SINAMICS G120XA converter
630 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB