7.3 Parameters
All objects: CUG120XA_USS
r0002 Drive operating display / Drv op_display
Access level: 2 Calculated: - Data type: Integer16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
200
Factory setting:
-
Description: Operating display for the drive.
Value: 0: Operation - everything enabled
10: Operation - set "enable setpoint" = "1" (p1142)
12: Operation - RFG frozen, set "RFG start" = "1" (p1141)
13: Operation - set "enable RFG" = "1" (p1140)
14: Operation - MotID, excitation running
16: Operation - withdraw braking with OFF1 using "ON/OFF1" = "1"
17: Operation - braking with OFF3 can only be interrupted with OFF2
18: Operation - brake on fault, remove fault, acknowledge
19: Operation - DC braking active (p1230, p1231)
21: Ready for operation - set "Enable operation" = "1" (p0852)
22: Ready for operation - de-magnetizing running (p0347)
31: Ready for switching on - set "ON/OFF1" = "0/1" (p0840)
35: Switching on inhibited - carry out first commissioning (p0010)
41: Switching on inhibited - set "ON/OFF1" = "0" (p0840)
42: Switching on inhibited - set "OC/OFF2" = "1" (p0844, p0845)
43: Switching on inhibited - set "OC/OFF3" = "1" (p0848, p0849)
44: Switching on inhibited - supply STO terminal w/ 24 V (hardware)
45: Switching on inhibited - remove fault, acknowledge fault
46: Switching on inhibited - exit commissioning mode (p0010)
70: Initialization
200: Wait for booting/partial booting
Dependency: See also: r0046
NOTICE
For several missing enable signals, the corresponding value with the highest number is displayed.
Note
OC: Operating condition
RFG: Ramp-function generator
COMM: Commissioning
MotID: Motor data identification
p0003 Access level / Acc_level
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C1, T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
3
Max:
4
Factory setting:
3
Description: Sets the access level to read and write parameters.
Value: 3: Expert
Parameters
7.3 Parameters
SINAMICS G120XA converter
352 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB