5.5 Restoring the factory settings
Why restore the factory settings?
Reset the converter to the factory settings in the following cases:
You do not know the converter settings.
The line voltage was interrupted during commissioning and you were not able to complete
commissioning.
Resetting to factory setting with the BOP-2 operator panel
Procedure
1. In the "Options" menu, select the "DRVRESET" entry
2. Confirm the reset using the OK key.
3. Wait until the converter has been reset to the factory setting.
You have reset the converter to the factory settings.
Commissioning
5.5 Restoring the factory settings
SINAMICS G120XA converter
124 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB