Frame
size
Height Height in‐
cluding
shield
plate
1)
Width Depth Additional depth Clearance
2)
With oper‐
ator panel
With G120
Smart Ac‐
cess
A B lateral front
FSH 1487 - 548 410 - - 200 200 30 100
FSJ 1438 - 801 410 - - 200 200 30 100
1)
The shield plates for FSD to FSG are available as options only.
2)
The cooling air clearances A and B refer to the converter without shield plate.
3)
Maximum surrounding air temperature during operation dependent on lateral clearance:
- Max. 55 °C for mounting with 0 mm lateral clearance (for tolerance reasons, we recommend a lateral clearance of approx.
1 mm.)
- Max. 60 °C for mounting with 50 mm lateral clearance.
Drill patterns (mm)
Table 3-1 FSA … FSG
Drill pattern Dimensions FSA FSB FSC FSD FSE FSF FSG
A 55 80 118 170 230 270 265
B 221.5 265 283 430 509 680 970.5
Ø 5 5 5.5 6.0 6.5 8.5 12.0
Fixings (bolts,
washers, nuts)
4 × M4 4 × M4 4 × M5 4 × M5 4 × M6 4 × M8 4 × M10
Tightening torque
(Nm)
2.5 2.5 2.5 6 10 25 50
Note: For the converters FSD to FSG, a printed drill pattern is supplied with each converter. This can be used to easily drill the
necessary mounting holes.
Mounting
3.3 Mounting the converter
SINAMICS G120XA converter
48 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB