r0054.0...15 CO/BO: Control word 1 / STW 1
Access level: 2 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Displays control word 1.
Bit field: Bit Signal name 1 signal 0 signal FP
00 ON/OFF1 Yes No -
01 OC / OFF2 No Yes -
02 OC / OFF3 No Yes -
03 Enable operation Yes No -
04 Enable ramp-function generator Yes No -
05 Continue ramp-function generator Yes No -
06 Enable speed setpoint Yes No -
07 Acknowledge fault Yes No -
08 Jog bit 0 Yes No 3030
09 Jog bit 1 Yes No 3030
10 Master control by PLC Yes No -
11 Direction reversal (setpoint) Yes No -
13 Motorized potentiometer raise Yes No -
14 Motorized potentiometer lower Yes No -
15 CDS bit 0 Yes No -
Note
The following control bits are displayed in r0054:
Bit 00: r0898 Bit 0
Bit 01: r0898 Bit 1
Bit 02: r0898 Bit 2
Bit 03: r0898 Bit 3
Bit 04: r0898 Bit 4
Bit 05: r0898 Bit 5
Bit 06: r0898 Bit 6
Bit 07: r2138 Bit 7
Bit 08: r0898 Bit 8
Bit 09: r0898 Bit 9
Bit 10: r0898 Bit 10
Bit 11: r1198 Bit 11
Bit 13: r1198 Bit 13
Bit 14: r1198 Bit 14
Bit 15: r0836 Bit 0
r0055.0...15 CO/BO: Supplementary control word / Suppl STW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 2513
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for supplementary control word.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Fixed setpoint bit 0 Yes No -
01 Fixed setpoint bit 1 Yes No -
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 367