4: PKW 4 words
127: PKW variable
Dependency: See also: p2030
Note
The parameter is not influenced by setting the factory setting.
p2024[0...2] Fieldbus interface times / Fieldbus times
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0 [ms]
Max:
10000 [ms]
Factory setting:
[0] 6000 [ms]
[1] 0 [ms]
[2] 0 [ms]
Description: Sets the time values for the fieldbus interface.
For Modbus the following applies:
p2024[0, 1]: Not relevant.
p2024[2]: Telegram pause time (pause time between two telegrams).
The following applies for BACnet:
p2024[0]: APDU timeout.
p2024[1, 2]: Not relevant.
Index: [0] = Max. processing time
[1] = Character delay time
[2] = Telegram pause time
Dependency: See also: p2020, p2030
Note
For p2024[2] (Modbus):
If the field bus baud rate is changed (p2020), the default time setting is restored.
The default setting corresponds to a time of 3.5 characters (dependent on the baud rate that has been set).
p2025[0...4] Fieldbus interface BACnet settings / BACnet setting
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
0
Max:
4194303
Factory setting:
[0] 1
[1] 5
[2] 3
[3] 32
[4] 0
Description: Sets the parameter for communication via BACnet.
p2025[0]:
Device object instance number (0 ... 4194303).
p2025[1]:
Maximum number of info frames (1 ... 10).
p2025[2]:
Number of APDU retries (0 ... 39).
p2025[3]:
Maximum master address (1 ... 127).
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 557