Dependency: The type of analog input AIx (voltage, current or temperature input) is set using p0756.
See also: p0756
Note
AI: Analog Input
p0753[0...3] CU analog inputs smoothing time constant / CU AI T_smooth
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
0.0 [ms]
Max:
1000.0 [ms]
Factory setting:
0.0 [ms]
Description: Sets the smoothing time constant of the 1st order lowpass filter for the analog inputs.
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
AI: Analog Input
T: Terminal
r0755[0...3] CO: CU analog inputs actual value in percent / CU AI value in %
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Displays the currently referred input value of the analog inputs.
When interconnected, the signals are referred to the reference quantities p200x and p205x.
Index: [0] = AI0 (X131 3/4)
[1] = AI1 (X131 10/11)
[2] = Reserved
[3] = Reserved
Note
AI: Analog Input
p0756[0...3] CU analog inputs type / CU AI type
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9566, 9568,
9576
Min:
0
Max:
4
Factory setting:
[0] 4
[1] 4
[2] 0
[3] 0
Parameters
7.3 Parameters
SINAMICS G120XA converter
432 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB