p3327[0...n] Fluid flow machine speed point 4 / Fluid_mach n4
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00
Max:
100.00
Factory setting:
75.00
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 4 as a [%].
Dependency: See also: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3328, p3329
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3328[0...n] Fluid flow machine power point 5 / Fluid_mach P5
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00
Max:
100.00
Factory setting:
100.00
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the power (P) of point 5 as a [%].
Dependency: See also: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3329
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3329[0...n] Fluid flow machine speed point 5 / Fluid_mach n5
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00
Max:
100.00
Factory setting:
100.00
Description: For the energy-saving display of a fluid-flow machine, a typical flow characteristic P = f(n) with 5 points along the
characteristic is required.
This parameter specifies the speed (n) of point 5 as a [%].
Dependency: See also: r0041, p3320, p3321, p3322, p3323, p3324, p3325, p3326, p3327, p3328
Note
The reference value for power and speed is the rated power/rated speed.
The energy saved is displayed in r0041.
p3330[0...n] BI: 2/3 wire control command 1 / 2/3 wire cmd 1
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2272, 2273
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for command 1 for the two-wire control/three-wire control.
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 647