r3859.0...1 CO/BO: Compound braking/DC quantity control status word / Comp-br/DC_ctr ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 6797
Min:
-
Max:
-
Factory setting:
-
Description: Display and connector output for the status word of the compound braking and DC quantity control.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Compound braking active Yes No -
01 DC quantity control active in the overmodulation range Yes No -
Dependency: See also: p3856
p3880 BI: ESM activation signal source / ESM act s s
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to activate the essential service mode (ESM) via digital input.
Using this function, when required the motor can be operated for as long as possible (e.g. to extract smoke).
BI: p3880 = 1 signal:
The essential service mode is activated.
BI: p3880 = 0 signal:
The essential service mode is deactivated.
Dependency: See also: p3881, p3882, p3883, p3884, r3889
WARNING
When activating the essential service mode (BI: p3880 = 1 signal), the motor immediately runs according to the
selected setpoint source. When the essential service mode is activated, the motor cannot be stopped using the OFF
commands.
Note
ESM: Essential Service Mode
Permissible signal sources:
- BO: r0722.x (high active)
- BO: r0723.x (low active), x = 0 ... 5, 11, 12
p3881 ESM setpoint source / ESM setp_src
Access level: 3 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
0
Max:
7
Factory setting:
0
Description: Sets the setpoint source for essential service mode (ESM).
Value: 0: Last known setpoint (r1078 smoothed)
1: Fixed speed setpoint 15 (p1015)
2: Control Unit analog input 0 (AI 0, r0755[0])
3: Fieldbus
4: Technology controller
6: Enable the response OFF1
7: Enable the response OFF2
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 653