p2016[0...3] CI: Comm IF USS PZD send word / Comm USS send word
Access level: 3 Calculated: - Data type: Unsigned32 /
Integer16
Can be changed: T, U Scaling: 4000H Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
0
Description: Selects the PZD (actual values) to be sent via the commissioning interface USS.
The actual values are displayed on an intelligent operator panel (IOP).
Index: [0] = PZD 1
[1] = PZD 2
[2] = PZD 3
[3] = PZD 4
p2020 Field bus interface baud rate / Field bus baud
Access level: 2 Calculated: - Data type: Integer16
Can be changed: T Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 9310
Min:
4
Max:
13
Factory setting:
8
Description: Sets the baud rate for the field bus interface (RS485).
Value: 4: 2400 baud
5: 4800 baud
6: 9600 baud
7: 19200 baud
8: 38400 baud
9: 57600 baud
10: 76800 baud
11: 93750 baud
12: 115200 baud
13: 187500 baud
Note
Fieldbus IF: Fieldbus interface
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected.
When p2030 = 1 (USS), the following applies:
Min./max./factory setting: 4/13/8
For p2030 = 2 (Modbus RTU), the following applies:
Min./max./factory setting: 5/13/7
For p2030 = 5 (BACnet MS/TP) the following applies:
Possible values/factory setting: (6, 7, 8, 10) / 8
If p2030 = 8 (P1), the following applies:
Min./max./factory setting: 5/7/5
Parameters
7.3 Parameters