p3884 CI: ESM setpoint technology controller / ESM setp tech_ctrl
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T, U Scaling: PERCENT Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source for the setpoint for p3881 = 4 (technology controller) in the essential service mode (ESM).
Dependency: See also: p3881
Note
ESM: Essential Service Mode
For p3884 = 0:
The technology controller uses the setpoint from p2253.
r3889.0...10 CO/BO: ESM status word / ESM ZSW
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7033
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the status word of the essential service mode (ESM).
Bit field: Bit Signal name 1 signal 0 signal FP
00 Essential service mode (ESM) activated Yes No -
01 Direction of rotation inverted Yes No -
02 Setpoint signal lost Yes No -
03 Technology controller actual value (p2264) lost Yes No -
04 Bypass active Yes No -
05 Setpoint technology controller parameterized (p3884) Yes No -
06 Technology controller during essential service mode active Yes No -
09 Response OFF1/OFF2 activated Yes No -
10 Automatic restart interrupted (F07320) Yes No -
Note
ESM: Essential Service Mode
p3900 Completion of quick commissioning / Compl quick_comm
Access level: 1 Calculated: - Data type: Integer16
Can be changed: C2(1) Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0
Max:
3
Factory setting:
0
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 655