r2169 CO: Actual speed smoothed signals / n_act smth message
Access level: 2 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: p2000 Dynamic index: -
Unit group: 3_1 Unit selection: p0505 Function diagram: 8010
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description: Display and connector output of the smoothed speed actual value for messages.
Dependency: See also: p2153
p2170[0...n] Current threshold value / I_thres
Access level: 3 Calculated:
CALC_MOD_LIM_REF
Data type: FloatingPoint32
Can be changed: T, U Scaling: p2002 Dynamic index: DDS, p0180
Unit group: 6_2 Unit selection: p0505 Function diagram: 8022
Min:
0.00 [Arms]
Max:
10000.00 [Arms]
Factory setting:
0.00 [Arms]
Description: Sets the absolute current threshold for the messages.
"I_act >= I_threshold p2170" (BO: r2197.8)
"I_act < I_threshold p2170" (BO: r2198.8)
Dependency: See also: p2171
p2171[0...n] Current threshold value reached delay time / I_thresh rch t_del
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 8022
Min:
0 [ms]
Max:
10000 [ms]
Factory setting:
10 [ms]
Description: Sets the delay time for the comparison of the current actual value (r0068) with the current threshold value (p2170).
Dependency: See also: p2170
p2172[0...n] DC link voltage threshold value / Vdc thresh val
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: p2001 Dynamic index: DDS, p0180
Unit group: 5_2 Unit selection: p0505 Function diagram: -
Min:
0 [V]
Max:
2000 [V]
Factory setting:
800 [V]
Description: Sets the DC link voltage threshold value for the following messages:
"Vdc_act <= Vdc_threshold p2172" (BO: r2197.9)
"Vdc_act > Vdc_threshold p2172" (BO: r2197.10)
Dependency: See also: p2173
p2173[0...n] DC link voltage comparison delay time / t_del Vdc
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0 [ms]
Max:
10000 [ms]
Factory setting:
10 [ms]
Description: Sets the delay time for the comparison of the DC link voltage r0070 with the threshold value p2172.
Dependency: See also: p2172
Parameters
7.3 Parameters
SINAMICS G120XA converter
594 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB