p29547[0...3] Multi-pump control continunous operating hours / Mpc Conti_oper_hrs
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T, U Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [h]
Max:
1000000.00 [h]
Factory setting:
0.00 [h]
Description: Displays the continuous operating hours for the motors.
The display can only be reset to zero.
Index: [0] = motor 1 operating hours
[1] = motor 2 operating hours
[2] = motor 3 operating hours
[3] = motor 4 operating hours
Note
Continuous operation is measured starting from when a motor is ON. It ends when a motor is OFF.
r29549 CO/BO: Multi-pump control feedback signal for contactor / Mpc fdb signal
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Bico to p1269[0] as a feedback signal
p29570[0...n] Ramp-up scaling 1 / RmpUpScaling1
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [%]
Max:
9999999.00 [%]
Factory setting:
100.00 [%]
Description: Sets the ramp-up scaling 1 for the dual ramp function [%].
p29571[0...n] Threshold speed 2 / Thresh_2_Ramp
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: p2000 Dynamic index: DDS, p0180
Unit group: 3_1 Unit selection: p0505 Function diagram: -
Min:
0.00 [rpm]
Max:
210000.00 [rpm]
Factory setting:
30.00 [rpm]
Description: Defines the threshold 2 for comparing the speed actual value with the speed threshold.
p29572[0...n] Ramp-up scaling 2 / RmpUpScaling2
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: T Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: -
Min:
0.00 [%]
Max:
9999999.00 [%]
Factory setting:
100.00 [%]
Description: Sets the ramp-up scaling 2 for the dual ramp function [%].
Parameters
7.3 Parameters
SINAMICS G120XA converter
712 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB