EasyManua.ls Logo

Siemens SINAMICS G120XA - Standard Drive Control

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5.4.5 Standard Drive Control
Select the motor standard:
KW / 50HZ: IEC
HP / 60HZ: NEMA, US units
KW / 60HZ: NEMA, SI units
Set the converter supply voltage.
Select the motor type. If a 5-digit motor code is stamped on the motor rating plate, select the
corresponding motor type with motor code.
Motors without motor code stamped on the rating plate:
INDUCT: Third-party induction motor
1L… IND: 1LE1, 1LG6, 1LA7, 1LA9 induction motors
Motors with motor code stamped on the rating plate:
1LE1 IND 100: 1LE1 . 9
1PC1 IND: 1PC1
Depending on the converter, the motor list in BOP‑2 can deviate from the list shown above.
If you have selected a motor type with motor code, you must now enter the motor code. The
converter assigns the following motor data corresponding to the motor code.
If you do not know the motor code, then you must set the motor code = 0, and enter motor data
from p0304 and higher from the rating plate.
87 Hz motor operation The BOP‑2 only indicates this step if you selected IEC as the motor
standard (EUR/USA, P100 = kW 50 Hz).
Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
Motor cooling:
SELF: Natural cooling
FORCED: Forced-air cooling
3
(8586$
3
,1992/7
3
0277<3(
3
027&2'(
+=
3
02792/7
3
027&855
3
02732:
3
027)5(4
3
027530
3
027&22/
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120XA converter
114 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB

Table of Contents

Related product manuals