p2223[0...n] BI: Technology controller fixed value selection bit 3 / Tec_ctrl sel bit 3
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 7950, 7951
Min:
-
Max:
-
Factory setting:
0
Description: Sets the signal source to select a fixed value of the technology controller.
Dependency: See also: p2220, p2221, p2222
r2224 CO: Technology controller fixed value effective / Tec_ctr FixVal eff
Access level: 3 Calculated: - Data type: FloatingPoint32
Can be changed: - Scaling: PERCENT Dynamic index: -
Unit group: 9_1 Unit selection: p0595 Function diagram: 7950, 7951
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description: Display and connector output for the selected and active fixed value of the technology controller.
Dependency: See also: r2229
r2225.0 CO/BO: Technology controller fixed value selection status word / Tec_ctr FixVal ZSW
Access level: 3 Calculated: - Data type: Unsigned16
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description: Display and BICO output for the status word of the fixed value selection of the technology controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Technology controller fixed value selected Yes No 7950,
7951
r2229 Technology controller number actual / Tec_ctrl No. act
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: - Scaling: - Dynamic index: -
Unit group: - Unit selection: - Function diagram: 7950
Min:
-
Max:
-
Factory setting:
-
Description: Displays the number of the selected fixed setpoint of the technology controller.
Dependency: See also: r2224
p2230[0...n] Technology controller motorized potentiometer configuration / Tec_ctr mop config
Access level: 3 Calculated: - Data type: Unsigned32
Can be changed: T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 7954
Min:
-
Max:
-
Factory setting:
0000 0100 bin
Description: Sets the configuration for the motorized potentiometer of the technology controller.
Bit field: Bit Signal name 1 signal 0 signal FP
00 Data save active Yes No -
02 Initial rounding-off active Yes No -
03 Non-volatile data save active for p2230.0 = 1 Yes No -
Parameters
7.3 Parameters
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 607