p1139[0...n] CI: Ramp-function generator ramp-down time scaling / RFG t_RD scal
Access level: 3 Calculated: - Data type: Unsigned32 /
FloatingPoint32
Can be changed: T Scaling: PERCENT Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 3070
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for scaling the ramp-down time of the ramp-function generator.
Dependency: See also: p1121
Note
The ramp-down time is set in p1121.
p1140[0...n] BI: Enable ramp-function generator/inhibit ramp-function generator / Enable RFG
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for the command "enable ramp-function generator/inhibit ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 4 (STW1.4).
BI: p1140 = 0 signal:
Inhibits the ramp-function generator (the ramp-function generator output is set to zero).
BI: p1140 = 1 signal:
Enable ramp-function generator.
Dependency: See also: r0054, p1141, p1142
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1141[0...n] BI: Continue ramp-function generator/freeze ramp-function generator / Continue RFG
Access level: 3 Calculated: - Data type: Unsigned32 / Binary
Can be changed: T Scaling: - Dynamic index: CDS, p0170
Unit group: - Unit selection: - Function diagram: 2501
Min:
-
Max:
-
Factory setting:
1
Description: Sets the signal source for the command "continue ramp-function generator/freeze ramp-function generator".
For the PROFIdrive profile, this command corresponds to control word 1 bit 5 (STW1.5).
BI: p1141 = 0 signal:
Freezes the ramp-function generator.
BI: p1141 = 1 signal:
Continue ramp-function generator.
Dependency: See also: r0054, p1140, p1142
CAUTION
When "master control from PC" is activated, this binector input is ineffective.
Parameters
7.3 Parameters
SINAMICS G120XA converter
486 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB