Maximum permissible motor cable length (Page 64)
NOTICE
Damage to the output reactor by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using the output reactor is 4 kHz. The output
reactor can be damaged if the pulse frequency is exceeded.
When using an output reactor, the pulse frequency of the converter must not be higher than
4 kHz.
NOTICE
Damage to the output reactor if it is not activated during commissioning
The output reactor may be damaged if it is not activated during commissioning.
Activate the output reactor during commissioning via the parameter specified by the
converter manufacturer.
Activate the output reactor during commissioning according to the electric specifications.
Note
Output reactors are available as optional components for converters of frame sizes FSD ... FSG
and FSH/FSJ only.
Article number
Converter frame size Rated power (kW) Output reactor
FSD 18.5 6SL3202-0AE23-8CA0
22 ... 37 6SE6400-3TC07-5ED0
45 6SE6400-3TC14-5FD0
FSE 55
FSF 75 ... 90
110 6SL3000-2BE32-1AA0
132 6SL3000-2BE32-6AA0
FSG 160 6SL3000-2BE33-2AA0
200 6SL3000-2BE33-8AA0
250 6SL3000-2BE35-0AA0
FSH 315 6SL3000-2AE36-1AA0
355 ... 400 6SL3000-2AE38-4AA0
FSJ 450 ... 500 6SL3000-2AE41-0AA0
560 6SL3000-2AE41-4AA0
Description
2.6 Optional components
SINAMICS G120XA converter
Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB 33