Parameters
Table 6-49 Minimum speed
Number Name Factory setting
p1051[C] CI: Speed limit of ramp-function generator, positive direction
of rotation
9733
p1052[C] CI: Speed limit of ramp-function generator, negative direction
of rotation
1086
p1080[D] Minimum speed 0 rpm
p1083[D] CO: Speed limit in positive direction of rotation 210000 rpm
r1084 CO: Speed limit positive active - rpm
p1085[C] CI: Speed limit in positive direction of rotation 1083
p1091[D] Skip speed 1 0 rpm
p1092[D] Skip speed 2 0 rpm
p1093[D] Skip speed 3 0 rpm
p1094[D] Skip speed 4 0 rpm
p1098[C] CI: Skip speed scaling 1
r1099 CO/BO: Skip frequency band of status word -
p1106 CI: Minimum speed signal source 0
r1112 CO: Speed setpoint according to minimum limit - rpm
r1114 CO: Setpoint after direction limiting - rpm
r1119 CO: Ramp-function generator setpoint at the input - rpm
r1170 CO: Speed controller setpoint sum - rpm
Further information is provided in the parameter list.
Parameters (Page 349)
NOTICE
Incorrect direction of motor rotation if the parameterization is not suitable
If you are using an analog input as speed setpoint source, then for a setpoint = 0 V, noise
voltages can be superimposed on the analog input signal. After the on command, the motor
accelerates up to the minimum frequency in the direction of the random polarity of the noise
voltage. A motor rotating in the wrong direction can cause significant material damage to the
machine or system.
Inhibit the motor direction of rotation that is not permissible.
Advanced commissioning
6.4 Setpoints and setpoint processing
SINAMICS G120XA converter
240 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB