Suppressing the automatic restart only functions for the setting p1210 = 6, 16 or 26.
Note
Motor starts in spite of an OFF command via the fieldbus
The converter responds with a fault if fieldbus communication is interrupted. For one of the
settings p1210 = 6, 16 or 26, the converter automatically acknowledges the fault and the motor
restarts, even if the higher-level control attempts to send an OFF command to the converter.
● In order to prevent the motor automatically starting when the fieldbus communication fails,
you must enter the fault number of the communication error in parameter p1206.
Parameter
Number Name Factory setting
p1206 Automatic restart faults not active 0
p1210 Automatic restart mode 0
p1211 Automatic restart, start attempts 3
p1212 Automatic restart, wait time start attempts 1 s
p1213[0] Automatic restart monitoring time
for restart
60 s
p1213[1] Reset automatic restart monitoring time for
start-up counter
0 s
p29630 Activate continuous operation 0
Advanced commissioning
6.8 Drive availability
SINAMICS G120XA converter