EasyManua.ls Logo

Siemens SINAMICS G120XA - Page 484

Siemens SINAMICS G120XA
918 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Note
The ramp-up time can be scaled via connector input p1138.
The parameter is adapted during the rotating measurement (p1960 > 0). This is the reason that during the rotating
measurement, the motor can accelerate faster than was originally parameterized.
For U/f control and sensorless vector control (see p1300), a ramp-up time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
p1120[0...n] Ramp-function generator ramp-up time / RFG ramp-up time
CUG120XA_USS
(PM330)
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C2(1), T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 3070
Min:
0.000 [s]
Max:
999999.000 [s]
Factory setting:
20.000 [s]
Description: The ramp-function generator ramps-up the speed setpoint from standstill (setpoint = 0) up to the maximum speed
(p1082) in this time.
Dependency: See also: p1082
Note
The ramp-up time can be scaled via connector input p1138.
The parameter is adapted during the rotating measurement (p1960 > 0). This is the reason that during the rotating
measurement, the motor can accelerate faster than was originally parameterized.
For U/f control and sensorless vector control (see p1300), a ramp-up time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
p1121[0...n] Ramp-function generator ramp-down time / RFG ramp-down time
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C2(1), T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 3070
Min:
0.000 [s]
Max:
999999.000 [s]
Factory setting:
10.000 [s]
Description: Sets the ramp-down time for the ramp-function generator.
The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to standstill
(setpoint = 0) in this time.
Further, the ramp-down time is always effective for OFF1.
Dependency: See also: p1082, p1127
Note
For U/f control and sensorless vector control (see p1300), a ramp-down time of 0 s does not make sense. The setting
should be based on the startup times (r0345) of the motor.
p1121[0...n] Ramp-function generator ramp-down time / RFG ramp-down time
CUG120XA_USS
(PM330)
Access level: 1 Calculated: - Data type: FloatingPoint32
Can be changed: C2(1), T, U Scaling: - Dynamic index: DDS, p0180
Unit group: - Unit selection: - Function diagram: 3070
Min:
0.000 [s]
Max:
999999.000 [s]
Factory setting:
30.000 [s]
Description: Sets the ramp-down time for the ramp-function generator.
The ramp-function generator ramps-down the speed setpoint from the maximum speed (p1082) down to standstill
(setpoint = 0) in this time.
Further, the ramp-down time is always effective for OFF1.
Dependency: The parameter is pre-assigned depending on the size of the power unit.
See also: p1082, p1127
Parameters
7.3 Parameters
SINAMICS G120XA converter
482 Operating Instructions, 03/2019, FW V1.0, A5E44751205B AB

Table of Contents

Related product manuals