LED Color State Description
Off No Ethernet connection
PNIO2 LED "RX/TX" Yellow On ---
Blinking PROFINET device sends/receives
frames
Off ---
1.4.5.1.5 Technical data
The system data of AC500 and S500
Ä
Chapter 2.6.1 “System data AC500” on page 971 are
applicable to the standard version.
The system data of AC500-XC
Ä
Chapter 2.7.1 “System data AC500-XC” on page 1023 are
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter Value
Protocol PROFINET IO RT
Bus connection 2 RJ45 (PNIO1 and PNIO2), with integrated 2-
port switch
Switch Integrated
Technology Hilscher NETX 100
Transfer rate 100 Mbit/s (full-duplex)
Transfer method According to Ethernet II, IEEE 802.3
Ethernet 100 base-TX, internal switch, 2x RJ45 socket
Bus length (segment length max.) 100 m
Indicators 5 LEDs
Usable terminal bases All TB5xx
All TB56xx (not TB5600)
Ä
Chapter 1.2.1
“TB56xx for AC500 V3 products” on page 4
Supported alarm types Process alarm, diagnostic alarm, return of Sub-
Module, plug alarm, pull alarm
Alarm processing Requires handling in application program
Current consumption from 24 V DC power
supply at the terminal base of the CPU
Typ. 85 mA
Internal supply Via the communication module interface of the
terminal base
Weight Ca. 170 g
Device specifications
Communication modules (AC500 standard) > PROFINET
2022/01/313ADR010278, 3, en_US120