EasyManua.ls Logo

ABB AC500 V3 - Channel parameters for the cam switch (max. 32 x); Group parameters for the digital part

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Channel parameters for the cam switch (max. 32x)
Name Value Internal value Internal value,
type
Default
camToTrack0
1
)
Digital Output
0 ... 15, none
0 ... 15, FF BYTE FF
: : : : :
camToTrack31 Digital Output
0 ... 15, none
0 ... 15, FF BYTE FF
1
) The value of the parameter camToTrack# defines which DO (digital output) is assigned to the
track. camToTrack0 = 3 for example means that track 0 is assigned to the digital output 3. If the
value FFh is set to a track, no digital output is assigned to it.
Name Value Referred FB from extended
Cam Switch Library
2
)
Internal
value
Internal
value,
type
Default
cam-
Type[0]
1
)
...
Common
Pulsed
Timed
Comfort
Cam shift
Binary shift
Multiturn cam
Time timed
Reference
Multiturn
timed
MCX_CamSwitchSimple_c
MCX_CamSwitchSimple_dc
MCX_PulseSwitch_dc
MCX_CamSwitchTimed_dc
MCX_CamSwitchComfort_dc
MCX_CamShift_dc
MCX_BinaryShift_dc
MCX_CamSwitchMulti_dc
MCX_SwitchTimeTimed_dc
MCX_BinaryReference_dc
MCX_CamSwitchMulti-
Timed_dc
0
1
2
3
4
5
6
7
8
9
BYTE 0
1
) camType additionally to camToTrack identifies the type of each cam switch and enables the
use of a specific function block from the Extended Cam Switch Library.
2
) camType parameters and the Extended Camswitch Library are only available for CI511-
ETHCAT and CI512-ETHCAT with device index C0 and above.
Group parameters for the digital part
Name Value Internal value Internal value,
type
Default
Input delay 0.01 ms
1 ms
8 ms
32 ms
0
1
2
3
BYTE 0.01 ms
0x00
Detect short cir-
cuit at outputs
Off
On
0
1
BYTE On
0x01
Device specifications
Communication interface modules (S500) > EtherCAT
2022/01/31 3ADR010278, 3, en_US 719

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals