Parameter Value
Output current
Rated current per channel (max.) 2.0 A (24 V DC resistance and general use,
100 V AC...240 V AC, resistance, general
use and pilot duty)
Rated current per group (max.) 6 A
Rated current (all channels together, max.) 12 A
Demagnetization when inductive loads are
switched off
External demagnetization measures must be
implemented when switching inductive loads.
Spark suppression with inductive AC loads Must be performed externally according to
driven load specification
Switching frequencies
With resistive loads Max. 1 Hz
With inductive loads On request
With lamp loads On request
Short-circuit-proof / Overload-proof No, should be provided by an external fuse
or circuit breaker
Rated protection fuse (for each channel) On request
Overload message No
Output current limitation No
Resistance to feedback against 24 V DC No
Connection of 2 outputs in parallel Not possible
Lifetime of relay contacts (cycles) 100,000 at rated load
Max. cable length *)
Shielded On request
Unshielded On request
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Technical data of the limit switch outputs
Parameter PM5012-T-ETH PM5012-R-ETH PM5032-T-ETH
PM5052-T-ETH
PM5072-
T-2ETH
PM5032-R-
ETH
PM5052-R-
ETH
Limit switch
Useable outputs 4 - 8 2
Fast output
max. 5 kHz
DO0 ... DO3 - DO0 … DO3 -
Fast output,
max. 100 kHz
- - DO4 … DO7 DC12 … DC13