EasyManua.ls Logo

ABB AC500 V3 - Ordering data; 1.6.3 Digital;Analog I;O modules; 1.6.3.1 S500; 1.6.3.1.1 DA501 - Digital;Analog input;output module

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Settling time for full range change (resistive
load, output signal within specified tolerance)
Typ. 5 ms
Conversion error of the analog values caused
by non-linearity, adjustment error at factory
and resolution within the normal range
Typ. ±0.5 % of full scale
at 25 °C
Max. ±1 % of full scale (all ranges)
at 0 °C...60 °C or EMC disturbance
Relationship between output signal and hex
code
See table,
Ä
Chapter 1.6.2.2.6.9.3 “Output
ranges voltage and current” on page 544
Unused outputs Can be left open-circuited
Ordering data
Part no. Description Product life cycle phase *)
1SAP 250 000 R0001 AX522, analog input/output module,
8 AI, 8 AO, U/I/Pt100, 12 bits + sign,
2-wires
Active
1SAP 450 000 R0001 AX522-XC, analog input/output
module, 8 AI, 8 AO, U/I/Pt100,
12 bits + sign, 2-wires, XC version
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
1.6.3 Digital/Analog I/O modules
1.6.3.1 S500
1.6.3.1.1 DA501 - Digital/Analog input/output module
16 digital inputs 24 V DC
8 configurable digital inputs/outputs 24 V DC, 0.5 A max.
4 analog inputs, voltage, current and RTD.
Resolution 12 bits plus sign
2 analog outputs, voltage and current
Resolution 12 bits plus sign
Fast counter
Module-wise galvanically isolated
XC version for use in extreme ambient conditions available
Device specifications
I/O modules > Digital/Analog I/O modules