Group parameters for the digital part
Name Value Internal value Internal value,
type
Default
Input delay 0.1 ms
1 ms
8 ms
32 ms
0
1
2
3
BYTE 0.1 ms
0x00
Detect short cir-
cuit at outputs
Off
On
0
1
BYTE On
0x01
Behaviour DO at
comm. error 
1
)
Off
Last value
Last value 5 sec
Last value 10 sec
Substitute value
Substitute value
5 sec
Substitute value
10 sec
0
1
6
11
2
7
12
BYTE Off
0x00
Substitute value
at output
0...65535 0000h...FFFFh WORD 0
0x0000
Preventive
voltage feedback
monitoring for
DC0..DC7 
2
)
Off
On
0
1
BYTE Off
0x00
Detect voltage
overflow at out-
puts 
3
)
Off
On
0
1
BYTE Off
0x00
Remarks:
1
)
The parameter Behaviour DO at comm. error is apply to DC and DO channels
and only analyzed if the Failsafe-mode is ON.
2
)
The state "externally voltage detected" appears, if the output of a channel
DC0...DC7 should be switched on while an externally voltage is connected.  In
this case the start up is disabled, as long as the externally voltage is connected.
The monitoring of this state and the resulting diagnosis message can be disabled
by setting the parameters to "OFF".
3
)
The error state "voltage overflow at outputs" appears, if externally voltage at
digital outputs DC0...DC7 and accordingly DO0...DO7 has exceeded the process
supply voltage UP3 
Ä
 Chapter 1.7.5.3.3 “Connections” on page 838 (see
description in section). The according diagnosis message "Voltage overflow on
outputs " can be disabled by setting the parameters on "OFF". This parameter
should only be disabled in exceptional cases for voltage overflow may produce
reverse voltage.
1.7.5.3.8  Diagnosis
Structure of the Diagnosis Block via PNIO_DEV_ALARM function block.
 
Communication interface modules (S500) > PROFINET
2022/01/313ADR010278, 3, en_US848