NOTICE!
Risk of damaging the PLC modules!
The PLC modules must not be removed while the plant is connected to a power
supply.
Make sure that all voltage sources (supply and process voltage) are switched
off before you
– connect or disconnect any signal or terminal block
– remove or replace a module.
NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
– Make sure that all voltage sources (supply voltage and process supply
voltage) are switched off before you begin with operations on the system.
– Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
The module provides several diagnosis functions
Ä
Chapter 1.6.2.1.2.6 “Diagnosis”
on page 366.
The following figures show the connection of RTDs to the inputs of the analog input module
AI562.
24 VDC
-
+
10
11
O0+
I0+
13
O1+
12
I0-
14
I1+
15
I1-
16
---
17
SG
18
SG
19
UP
20
ZP
24 VDC
-
+
10
11
O0+
I0+
13
O1+
12
I0-
14
I1+
15
I1-
16
---
17
SG
18
SG
19
UP
20
ZP
2-wires input 3-wires input
With 2-wires connection, the resistance of the connection wires influences the
accuracy of the measured value. Use 3-wires connection to achieve the guaran-
teed measuring accuracy.
The meaning of the LEDs is described in the Displays section
Ä
Chapter 1.6.2.1.2.7 “State
LEDs” on page 367.
I/O configuration
The analog input module AI562 does not store configuration data itself.