Parameter Value
With inductive loads On Request
With lamp loads Max. 1 Hz
Output type Non-protected
Protection type
External fuse
1
)
Rated protection fuse 5 A fast
Short-circuit-proof / Overload-proof No, should be provided by an external fuse or circuit
breaker
Overload message No
Output current limitation No
Connection of 2 outputs in parallel Not possible
Lifetime of relay contacts (cycles) 100.000 at rated load
Max. cable length
Shielded 500 m
Unshielded 150 m
1
) Per group in case of group fuse protection. For each channel in case of channel-by-channel
fuse protection. The maximum current per group must not be exceeded.
Ordering data
Part no. Description Product life cycle phase *)
1TNE 968 902 R2302 DX571, digital input/output module,
8 DI 24 V DC / 24 V AC, 8 DO, relay
output
Active
1TNE 968 901 R3101 Terminal block TA563-9, 9 pins, screw
front, cable side, 6 pieces per unit
Active
1TNE 968 901 R3102 Terminal block TA563-11, 11 pins,
screw front, cable side, 6 pieces per
unit
Active
1TNE 968 901 R3103 Terminal block TA564-9, 9 pins, screw
front, cable front, 6 pieces per unit
Active
1TNE 968 901 R3104 Terminal block TA564-11, 11 pins,
screw front, cable front, 6 pieces per
unit
Active
1TNE 968 901 R3105 Terminal block TA565-9, 9 pins, spring
front, cable front, 6 pieces per unit
Active
1TNE 968 901 R3106 Terminal block TA565-11, 11 pins,
spring front, cable front, 6 pieces per
unit
Active
*) Modules in lifecycle Classic are available from stock but not recommended